NETYS RT

NETYS RT

Total protection on rack or tower
Single/single phase UPS from 1100 to 11000 VA

The solution for

• Servers and networking devices
• VoIP communication systems
• Structured cabling systems
• Video surveillance systems
• Control systems
• Switching
• Edge data centres

Advantages

Simple to install

• No configuration necessary on first startup.
• Space and time saving ‘tower-to-rack’ conversion mode.
• Compact footprint (tower mode).
• High density rack enclosure saving valuable cabinet rack space.

High protection and availability

• Online double conversion technology with sinusoidal waveform, completely filters out all disturbances from / to the mains power supply and ensures maximum protection of the utility.
• Wide tolerance of the input voltage reduces switchovers to battery mode, prolonging battery life.
• Possibility of 1+1 parallel and redundant configuration to maximise the availability of critical utilities (up to 22 kVA).
• Hot-swap plug-in manual bypass.

Certified performance

• Performance tested and verified by independent laboratory.
• Full performance up to 40 °C without derating.

Easy to use

• Clear and uncluttered multilanguage LCD display.
• Wide range of communication protocols for integration into LAN networks or Building Management Systems.
• IoT ready device for access to connected services.
• Load segmentation function to prioritize loads and manage critical situations.

Extended and flexible back-up time

• Hot-swap modular battery extension (EBM) to meet all back-up time requirements, even after installation.
• Battery ageing detection function.
• Fast recharge - even for very long back-up time.
• Li-Ion battery technology-ready.

 

  • Standard and option features

  • Technical Data

    Connections

     

    connections-netys-rt3.jpg

    1. Mains input socket (IEC 320)
    2. Fan
    3. Output socket (full power)
    4. Input to power off the UPS remotely
    5. RS232 interface (MODBUS protocol)
    6. USB port
    7. Input protection
    8. Output sockets (IEC 320 - 10 A)
    9. Connector for external battery extension
    10. Slot for optional communication boards
    11. Battery extension connector
    12. Output terminals
    13. Input terminals
    14. Input switch
    15. Parallel port connector
    16. Dry contact interface
    17. RS485 for Li-ion battery BMS

     

    Control panel

     

    control-panel-netys-rt3.jpg

    1. Yellow LED lit. Operation in bypass mode
    2. Green LED lit. Mains healthy
    3. OFF button
    4. Green LED lit. Normal operation (inverter in-line)
    5. ON/TEST and buzzer override button
    6. Navigator button
    7. Alphanumeric LCD display
    8. Green LED lit. Status of the load
    9. Load status
    10. Configuration
    11. Programmable outlets
    12. Battery status
    13. Load level (5 steps)
    14. Buzzer off
    15. Load present
    16. Battery fault / Replace the battery
    17. General alarm
    18. Overload
    19. Input and output values
    20. Normal mode / Battery mode (flashing)

     

    Technical data

     

    Power 1100 VA / 900 W 1700 VA / 1350 W 2200 VA / 1800 W 3300 VA / 2700 W 5000 VA / 5000 W 7000 VA / 6000 W 9000 VA / 8000 W 11000 VA / 10000 W
    Architecture online double conversion VFI with input PFC and automatic bypass
    Parallel redundant function - - - - 1+1 1+1 1+1 1+1
    Input
    Voltage 230 V (1ph) 120÷280 V; (175÷280 V @100% load)  230 V (1ph) 100÷280 V; (175÷280 V @100% load)
    Frequency 50/60 Hz +/-10% (Auto-Selectable)  40/70 Hz (50/60 Hz +/-10% Auto-Selectable)
    Power factor / THDi >0.99 / <5%  >0.99 / <3%
    Input socket IEC 320-C14 (10 A) IEC 320-C20 (16 A) terminals
    Output
    Voltage 230 V (1ph) selectable 200 / 208 / 220 / 240 V - 50 or 60 Hz + /- 2 % (+/- 0.05 Hz in battery mode)
    Power factor 0.9
    @ 1000 VA
    0.9
    @ 1500 VA
    0.9
    @ 2000 VA
    0.9
    @ 3000 VA
    1
    @ 5000 VA
    1
    @ 6000 VA
    1
    @ 8000 VA
    1 @ 10000 VA
    Efficiency (online mode) up to 93% online mode up to 95,5% online mode
    Overload capability up to 105% continuously; 125% x 3 min; 150% x 30 sec up to 105% continuously; 125% x 2 min; 150% x 30 sec
    Output connections 6 x IEC 320-C13 (10 A) 6 x IEC 320-C13 (10 A) + 1 x IEC 320-C19 (16 A) terminals
    Battery
    Standard autonomy(1) 7 11 8 9 13 8 12 9
    Voltage 24 VDC 48 VDC 48 VDC 72 VDC 192 VDC 192 VDC 240 VDC 240 VDC
    Recharge time < 3h to recover 90% capacity < 6h to recover 90% capacity
    Communication
    Mimic panel LCD with graphical icons  LCD with menu available in 10 languages
    RS232 MODBUS protocol  •
    USB port
    WEB / SNMP (Ethernet RJ45 port) option option option option option option option option
    COMM slot
    Dry contacts option option option option
    EPO input
    Parallel port - - - -
    Standards
    Safety IEC/EN 62040-1, AS 62040.1.1, AS 62040.1.2
    EMC IEC/EN 62040-2, AS 62040.2
    Performance IEC/EN 62040-3 (efficiency tested by an external independent body)
    Product declaration(2) CE, RCM (E2376)
    Environment
    Operating ambient temperature from 0 °C to +40 °C (up to 45 °C (3))
    Storage temperature range from -15 °C to +55 °C (from 15 °C to 25 °C for best battery life)
    Relative Humidity 5-95% non-condensing
    Noise level (ISO 3746) < 45 dBA <50 dBA < 55 dBA
    Dimensions & weight
    UPS size std (W x D x H) 89 x 332 x 440 mm 89 x 430 x 440 mm 89 x 430 x 440 mm 89 x 608 x 440 mm 89 x 430 x 440 mm 89 x 430 x 440 mm 89 x 565 x 440 mm 89 x 565 x 440 mm
    UPS size RACK 2U 2U 2U 2U 2U 2U 2U 2U
    UPS weight std 13 kg 18 kg 19 kg 30 kg 11 kg 12 kg 16 kg 17 kg
    IP rating IP20
    EBM module size (W x D x H) 89 x 332 x 440 mm 89 x 430 x 440 mm 89 x 608 x 440 mm 89 x 565 x 440 mm 131 x 650 x 440 mm
    EBM module RACK 2U 2U 2U 2U 2U 2U 3U 3U
    EBM module weight 16 kg 29 kg 29 kg 43 kg 39 kg 39 kg 67 kg 67 kg

    (1) @ 75% of nominal load PF 0.7. 
    (2) BIS compliance for 5000 VA and 7000 VA models
    (3) Conditions apply.