Strong Points
Function
Delphys XL is a highly compact UPS with best in class efficiency offering inherent redundancy and allowing by design, fast & safe maintenance operation. A fully resilient UPS architecture eliminating traditional single points of failure.
Conformity to standards
EN/IEC 62040-1
EN/IEC 62040-2
EN/IEC 62040-3
EN/IEC 62040-4
Advantages
Flexible integration with an optimised footprint
- High power UPS packed into a compact and optimised design.
- Highly flexible connection to your electrical environment.
- Easy and fast deployment of the entire UPS system.
- Up to 70% space saving when combined with lithium-ion batteries.
- Advanced on-site testing features to certify commissioning.
Unmatched resiliency to maximise availability
- UPS architecture eliminates single point of failure related to traditional monolithic UPS.
- Fault tolerant concept provides double conversion mode redundancy up to 80% of the rated power.
- Self-sufficient power bricks with advanced selective disconnection.
- Based on our field proven high power XL platform.
- Limited number of power converters - each designed to eliminate potential fault propagation for best MTBF.
- Powerful and robust static bypass.
Best in class energy management & savings
- 99,1% efficiency with our Smart Conversion Mode.
- 97,1% VFI mode as standard.
- ENERGY SAVER for higher system efficiency under low load conditions (bricks in hot stand-by).
- Multiple advanced operating and testing mode to minimise TCO.
- Ready for grid support functionalities.
Critical chain interoperability
- Designed to fit any data centre power distribution architecture.
- Advanced functionalities to ensure Genset stability upon restart or significant variation in loads.
- Designed to coordinate perfectly with our downstream connected STS.
- Supports even the most challenging load variation.
Easy and safe maintenance supporting low MTTR
- Reduced MTTR supported by cold-extractible power bricks.
- No cabling operation required to slide-out a power brick.
- Front access to all components.
- Safe servicing thanks to “hands outside” maintenance.
- Maintenance station with embedded operating power brick as a spare.
- Option to test the UPS and batteries without load when carrying out maintenance activities.
Technical characteristics
General characteristics | ||
---|---|---|
UPS power rating (35 °C) | 1000 kVA / kW | 1200 kVA / kW |
Efficiency in Double Conversion Mode | Up to 97.1% - certified by third party (TÜV) | |
Efficiency in Smart Conversion Mode | Up to 99.1% - certified by third party (TÜV) | |
Parallel capability | Up to 4 units |
Inputs | ||
---|---|---|
Nominal input voltage | 380 / 400 / 415V - 3Ph or 3Ph+N | |
Input voltage tolerance | 200 to 480V | |
Input connection | Common or separated / top or bottom | |
Frequency range | 50/60Hz ± 10% | |
Input power factor / THDi | > 0.99 / < 1.5% @ full load | |
Power walk-in on Genset | Linear ramp - from 1A/sec to 1000A/sec |
Output | ||
---|---|---|
Nominal output voltage | 380 / 400 / 415V - 3Ph or 3Ph+N | |
Frequency range | 50/60Hz ± 0.01% (free running) | |
Voltage regulation | ± 1% steady state | |
Output voltage distortion (THDv) | < 1% | |
Output voltage performance (load variation 0 - 100%) | Complies with IEC 62040-3 Class 1 (VFI-SS-111) | |
Inverter overload capability | 110% 1h / 125% 10 min / 150% 1 min | |
Bypass overload capability | 110% continuous / 125% 10 min / 150% 1 min | |
Inverter short circuit capability | Up to 3230A | Up to 4090A |
Bypass short circuit selectivity | Fuseless architecture (Icw 65kA) |
Batteries | ||
---|---|---|
Battery type - 2 wires (+/-) | VRLA / Lithium-ion | |
Battery voltage range | Up to 705V | |
Battery connection capability | Up to 10 strings (w/o extra cabinet) | |
Lithium-ion communication | Modbus TCP / dry contact |
Environment | ||
---|---|---|
Operating temperature | 0 - 40°C | |
Humidity | 0 - 95% without condensation | |
Air flow | From front to top | |
Maximum altitude without derating | 1000m (3,300 ft) | |
Standard protection rating | IP20 / IP21 (optional) | |
Seismic rating | Zone 2 / Zone 4 (optional) | |
Frame colour | RAL 7016 |
Compliance with standards | ||
---|---|---|
Safety | IEC/EN 62040-1 | |
EMC | IEC/EN 62040-2 | |
Performance | IEC/EN 62040-3 | |
Environmental | IEC/EN 62040-4 |
Dimensions and weight | ||
---|---|---|
UPS dimensions (W x D x H) | 2625 x 1000 x 2005 mm | 3003 x 1000 x 2005 mm |
Weight | 2600 kg | 3200 kg |
Clearance | No rear or lateral clearance for installation and maintenance |
System
Electrical options
- Input, output and maintenance bypass switches.
- PEN kit for TN-C grounding system.
- Reinforced battery charger.
- Battery protection tripping kit.
- SMART CONVERSION mode.
- BCR (Battery Capacity Re-injection).
- ACS synchronisation system.
- Cold start.
- Maintenance Station with spare power conversion brick.
- Advanced Genset Management.
Communication
Standard communication features
- User-friendly 7” touch-screen multilingual colour graphic display.
- USB port to download UPS reports and log files.
- Ethernet port for service purposes.
Communication options
- Dry-contact interface (configurable voltage-free contacts).
- MODBUS RTU RS485 or TCP.
- BACnet/IP interface.
- NET VISION: professional WEB/SNMP Ethernet interface for secure UPS monitoring and remote automatic shutdown.
- NET VISION EMD: Environment Temperature and Humidity sensor with 2 inputs.
- Remote View Pro supervision software.
- Remote touch-screen panel.