Strong Points
Function
Specially engineered to power and protect typical industrial equipments such as motors, motor speed drivers, lamps, non linear loads, welding equipments, power supplies, MASTERYS IP+ is also perfectly able to supply control equipments like programmable controllers, sensors and measurement apparatus and integrates perfectly into the most demanding industrial environments.
Conformity to standards
IEC/EN 62040, IEC/EN 62040-1, IEC/EN 62040-3
AS 62040.1.1, AS 62040.1.2, AS 62040.2, AS 62040.3
CE
RCM (E2376)
Superior
Best in class & certified performance to optimise usage and Total Cost of Ownership.
Advantages
Designed for the most demanding applications
- Designed to protect industrial processes.
- A compact solution with isolation transformer and integrated batteries.
- Robust enclosure (2 mm thick heavy steel structure).
- Floor anchoring (to prevent tilting).
- Standard IP31 protection degree.
- Dust and water splash resistant enclosure (IP52) with easy replaceable dust filters (option).
- Operation at temperature up to 50 °C.
- Wide input voltage tolerance from -40 % up to +20 % of nominal voltage.
- Double EMC immunity compared to UPS international standard IEC 62040-2.
- Double overvoltage protection.
Process continuity
- Frontal access for input/output cabling, spares replacement and preventative maintenance.
- Scalable power and high availability (using redundancy), with the facility to parallel up to 6 units.
Easy integration into industrial networks
- Input power factor - 0.99 and input current harmonic distortion < 3% thanks to IGBT rectifier.
- Compatible with Open Vented Lead Acid, Valve Regulated Lead Acid (VRLA) and Nickel Cadmium batteries.
- User-friendly multilingual interface with graphic display.
- Flexible communication boards for every industrial communication need: dry contacts, MODBUS, PROFIBUS, etc.
- Fully compatible with generator sets.
- K-rated galvanic isolation transformer embedded.
- Adaptation to typical industrial voltages (input and output).
Applications
- Infrastructure & Transport - Power for railway signaling
- Industry - Power availability for industrial process
Technical data
Sn [kVA] | 10 | 15 | 20 | 30 | 40 | 60 | 80 |
Pn [kW] - 3/1 | 9 | 13,5 | 18 | 27 | 32 | 48 | - |
Pn [kW] - 3/3 | 9 | 13,5 | 18 | 27 | 36 | 48 | 64 |
Parallel configuration(1) | up to 6 units |
Input | |||||||
---|---|---|---|---|---|---|---|
Model | 10 | 15 | 20 | 30 | 40 | 60 | 80 |
Rated voltage | 400V | ||||||
Voltage tolerance | ±20%(2) (up to -40% @ 50% of rated power) | ||||||
Rated frequency | 50/60Hz | ||||||
Frequency tolerance | ±10% | ||||||
Power factor/THDI(3) | 0.99/<3% |
Output | |||||||
---|---|---|---|---|---|---|---|
Model | 10 | 15 | 20 | 30 | 40 | 60 | 80 |
Rated voltage | 1ph + N: 230V (can be configured 220/240V) 3ph + N: 400V (380/415V configurable) |
||||||
Voltage tolerance | ±1% | ||||||
Rated frequency | 50/60Hz | ||||||
Frequency tolerance | ±2% (configurable from 1% to 8% with generating set) | ||||||
Total output voltage distortion - linear load | <1% | ||||||
Total output voltage distortion - non-linear load | <5% | ||||||
Overload(2) | 125% for 10 minutes, 150% for 1 minute(2) | ||||||
Crest factor | 3:1 (complying with IEC 62040-3) |
Bypass | |||||||
---|---|---|---|---|---|---|---|
Model | 10 | 15 | 20 | 30 | 40 | 60 | 80 |
Rated voltage | 1ph + N: 230V, 3ph + N: 400V | ||||||
Voltage tolerance | ±15% (configurable from 10% to 20% with generating set) | ||||||
Rated frequency | 50/60Hz | ||||||
Frequency tolerance | ±2% (configurable from 1% to 8% with generating set) |
Environment | |||||||
---|---|---|---|---|---|---|---|
Model | 10 | 15 | 20 | 30 | 40 | 60 | 80 |
Operating ambient temperature | from 0°C up to +50°C(2) (from 15°C to 25°C for maximum battery life) | ||||||
Relative humidity | 0%-95% without condensation | ||||||
Maximum altitude | 1000m without derating (max. 3000m) | ||||||
Acoustic level at 1m (ISO 3746) |
<52dBA | <55dBA | <65dBA |
UPS cabinet | |||||||
---|---|---|---|---|---|---|---|
Model | 10 | 15 | 20 | 30 | 40 | 60 | 80 |
Dimensions (3/1) W x D x H (mm) | 600 x 800 x 1400 | 1000 x 835 x 1400 | - | ||||
Dimensions (3/3) W x D x H (mm) | 600 x 800 x 1400 | 1000 x 835 x 1400 | |||||
Weight (3/1) (kg) | 230 | 250 | 270 | 330 | 490 | 540 | - |
Weight (3/3) (kg) | 230 | 250 | 270 | 320 | 370 | 500 | 550 |
Degree of protection | IP31 and IP52 (according to IEC 60529) | ||||||
Colours | RAL 7012 |
Standards | |||||||
---|---|---|---|---|---|---|---|
Model | 10 | 15 | 20 | 30 | 40 | 60 | 80 |
Safety | IEC/EN 62040-1, AS 62040.1.1, AS 62040.1.2 | ||||||
Type and performance | IEC/EN 62040-2, AS 62040.2 | ||||||
EMC | IEC/EN 62040-3, AS 62040.3 | ||||||
Product declaration | CE, RCM (E2376) |
(1) With transformer on input/bypass side.
(2) Conditions apply.
(3) At source THDV <2% and nominal load.
More technical data on the dedicated sales document.
System
Electrical options
- Long-life batteries.
- External battery cabinet (degree of protection up to IP32).
- External temperature sensor.
- Additional battery chargers.
- Additional transformer.
- Parallel kit.
- Cold start.
- ACS synchronization system.
- Neutral creation kit for mains without neutral.
- Tropicalization and anti-corrosion protection for electrical boards.
Communication
Standard communication features
- Multilanguage graphic display.
- MODBUS RTU.
- Dry-contact interface (configurable voltagefree contacts).
- Ethernet interface for UPS monitoring via WEB pages.
Communication options
- 2 slots for communication options.
- MODBUS RTU RS485 or MODBUS TCP.
- PROFIBUS / PROFINET gateway.
- BACnet/IP interface.
- NET VISION: professional WEB/SNMP Ethernet interface for secure UPS monitoring and remote automatic shutdown.
- REMOTE VIEW PRO supervision software
- IoT gateway for Socomec cloud services and SoLive UPS mobile app.