Strong Points
Function
With its flexible modularity providing seamless and risk-free power scalability up to 200 kW, the MODULYS GP range is the ideal solution for unscheduled site upgrades or incremental power evolutions. The installed power can be increased up to 200 kW by adding hot-swap plug-in power modules for incremental steps of 25 kW.
Designed with no single point of failure, the MODULYS GP offers all the advantages of the Green Power 2.0 technology.
Conformity to standards
IEC/EN 62040-1, IEC/EN 62040-2, IEC/EN 62040-3, IEC 60068-2-57, IEC/EN 62040-4
AS 62040.1.1, AS 62040.1.2, AS 62040.2, AS 62040.3
CE
RCM (E2376)
EAC
Ultimate
Fully redundant architecture for maximum availability, minimum MTTR and risk free maintenance.
Advantages
Fully modular system
- Plug-in power module.
- Plug-in battery module.
- Plug-in auxiliary mains bypass module.
- Top or bottom connection.
- Top-air exhaust module.
Totally redundant design
- N+1, N+x redundancy level.
- Designed for no single point of failure.
- No centralised parallel control.
- Totally independent power modules.
- Redundant parallel bus connection (ring configuration).
Automatic firmware allignment
- Without human intervention.
- Completely risk-free.
- Load protected in inverter mode.
Enhanced serviceability performance
- Power module automatic firmware alignment.
- Fast & safe maintenance based on hotswap parts (power modules, auxiliary mains bypass, electronic boards).
- Battery can be hot-swapped without shutting down the connected equipment.
- Ready for concurrent maintenance.
‘Forever Young’ concept
- Exclusive life cycle extension programme.
- Eliminates end-of-life criticality.
- Based on an electronics-free cabinet + a set of plug-in parts.
- Module compatibility guaranteed for 20+ years.
- Allows for the implementation of future module technology.
- Company declaration of 20-year compatibility.
Applications
- Data center - Power availability for servers
- Data center - Power availability for telecom
- Data center - Power availability for edge
- Healthcare - Critical power for operating theatre
Technical data
UPS system | |||
---|---|---|---|
Power [Sn] | 25 to 200kVA | 25 to 400kVA | 25 to 600kVA |
Power [Pn] | 25 to 200kW | 25 to 400kW | 25 to 600kW |
Number of power modules | 1 to 8 | 1 to 16 | 1 to 24 |
Input / output | 3/3 | ||
Redundant configuration | N+x |
Input | |||
---|---|---|---|
Model | 25 to 200kVA | 25 to 400kVA | 25 to 600kVA |
Voltage | 400V 3ph (340V to 480V) | ||
Frequency | 50/60Hz ±10% | ||
Power factor/THDI | >0.99/<1,5% |
Output | |||
---|---|---|---|
Model | 25 to 200kVA | 25 to 400kVA | 25 to 600kVA |
Power factor | 1 (according to IEC/EN 62040-3) | ||
Voltage | 380/400/415V ±1% 3ph+N | ||
Frequency | 50/60Hz ±0.1% | ||
Voltage distortion | <1% (linear load), <3% (non-linear load according lEC 62040-3) | ||
Short-circuit current | up to 3 x In | ||
Overload | 125% for 10 minutes, 150% for 1 minute | ||
Crest factor | 3:1 |
Bypass | |||
---|---|---|---|
Model | 25 to 200kVA | 25 to 400kVA | 25 to 600kVA |
Voltage | rated output voltage ±15% (configurable with from 10% to 20%) | ||
Frequency | 50/60Hz ±2% (configurable for GenSet compatibility) |
Efficiency (TÜV SÜD verified) | |||
---|---|---|---|
Model | 25 to 200kVA | 25 to 400kVA | 25 to 600kVA |
Online double conversion mode | up to 96.5% |
Environment | |||
---|---|---|---|
Model | 25 to 200kVA | 25 to 400kVA | 25 to 600kVA |
Ambient temperature | 0°C to 40°C (15 to 25°C for maximum battery life) | ||
Relative humidity | 0 to 95% without condensation | ||
Maximum altitude | 1000m without derating (3000m max) | ||
Acoustic level at 1m | <55dBA |
System Cabinet | |||
---|---|---|---|
Model | 25 to 200kVA | 25 to 400kVA | 25 to 600kVA |
Width (mm) | 600 | 2 x 600 (combinable system) | 3 x 600 (combinable system) |
2010 (fully integrated solution) | 2610 (fully integrated solution) | ||
Depth (mm) | 890 | ||
Height (mm) | 1975 | ||
Weight (empty cabinet) (kg) | 210 | 2 x 210 (combinable system) | 3 x 210 (combinable system) |
780 (fully integrated solution) | 1010 (fully integrated solution) | ||
Degree of protection | IP20 |
Standards | |||
---|---|---|---|
Model | 25 to 200kVA | 25 to 400kVA | 25 to 600kVA |
Safety | IEC/EN 62040-1, AS 62040.1.1, AS 62040.1.2 | ||
EMC | IEC/EN 62040-2 Class C2, AS 62040.2 | ||
Performance | VFI-SS-111, IEC/EN 62040-3, AS 62040.3 | ||
Seismic compliance | Uniform Building Code UBC:1997, IEC 60068-2-57:2013 | ||
Environmental | IEC/EN 62040-4 | ||
Product certification | CE, RCM (E2376) |
Power module | |||
---|---|---|---|
Model | 25 to 200kVA | 25 to 400kVA | 25 to 600kVA |
Height | 3U | ||
Weight (kg) | 34 | ||
Type | Hot plug-in / Hot-swappable | ||
MTBF | >1000000 hours (calculated and verified) |
System
Electrical options
- External battery cabinet.
- High capacity battery charger.
- ACS synchronisation system.
- Internal backfeed isolation device.
Communication
Standard communication features
- User-friendly 7" touch-screen multilingual colour graphic display.
- 2 slots for communication options.
- USB port to download UPS report and log file.
- Ethernet port for service purpose.
- Commissioning wizard.
Communication options
- Dry-contact interface.(configurable voltage-free contacts).
- MODBUS RTU RS485 or MODBUS.
- BACnet/IP interface.
- NET VISION: professional WEB/SNMP Ethernet interface for secure UPS monitoring and remote automatic shutdown.
- REMOTE VIEW PRO supervision software.
- IoT gateway for Socomec cloud services and SoLive UPS mobile app.
- Remote touch-screen panel.