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

Classification

UNSPSC 39122205
ETIM Class EC000216
IGCC 5177

Commerce

Description Remotely Operated Transfer Switch ATyS r, switching type I-0-II, frame B8, 4P 2000A, with positive break indication and replaceable motor, back plate mounting
Effective date 2021-08-10
Offer Life Cycle Code 40
Country of origin FR

ETIM - Electrical characteristics

Max. rated operation voltage Ue AC [V] 1000
Rated operating voltage [V] 400..690
Rated permanent current Iu [A] 2000
Rated permanent current at AC-23, 400 V [A] 1600
Rated permanent current at AC-21, 400 V [A] 2000
Rated short-time withstand current lcw [kA] 50
Rated operation power at AC-23, 400 V [kW] 900
Switching power at 400 V [kW] 12800
Number of poles 4

ETIM - Mechanical characteristics

Suitable for floor mounting No
Suitable for front mounting 4-hole No
Suitable for front mounting centre No
Suitable for distribution board installation No
Suitable for intermediate mounting Yes
Colour control element Other
Degree of protection (IP), front side IP20
Width [mm] 716
Height [mm] 258
Depth [mm] 521

ETIM - Technical features

Version as main switch Yes
Version as maintenance-/service switch Yes
Version as safety switch Yes
Version as emergency stop installation No
Version as reversing switch Yes
Number of switches 2
Number of auxiliary contacts as normally open contact 3
Number of auxiliary contacts as change-over contact 4
Motor drive optional No
Motor drive integrated Yes
Voltage release optional No
Device construction Built-in device fixed built-in technique
Type of control element Other
Interlockable Yes
Type of electrical connection of main circuit Bolt connection

Logistics

Customs number 8536508000
Price unit PC

Norms

Conformity to standards
  • CCC
  • IEC

Technical Characteristics

Height [mm] 258
Width [mm] 716
Depth [mm] 521
Weight [kg] 78
Control operator RTSE
Number of poles 4
Rated current [A] 2000
Type Class PC
Frame size B8

Documentation

  • PDF